Model GR1000E 9/12kW
Low Speed
Maximum door width m 1
Maximum mounting height m 3
Maximum air volume m3/h 1150
Maximum velocity m/s 6.4
Motor power W 365
Noise level @ 3m free field dB(A) 52
Electric Heated
Heating capacity - std/max1 kW 9/12
Electrical supply 415V 3ph 50Hz
Total electrical load -per phase
Standard - as supplied A 13.7
Maximum - selectable by installer A 17.9
Weight kg 34.5
Medium Speed
Maximum door width 1
Maximum mounting height 3
Maximum air volume 1440
Maximum velocity 8
Motor power 365
Noise level @ 3m free field 55
Heating capacity - std/max1 kW 9/12
Electrical supply 415V 3ph 50Hz
Total electrical load -per phase
Standard - as supplied A 13.8
Maximum - selectable by installer A 18
Weight kg 34.5
High Speed
Maximum door width 1
Maximum mounting height 4
Maximum air volume 1800
Maximum velocity 10
Motor power 365
Noise level @ 3m free field 59
Heating capacity - std/max1 9/12
Electrical supply 415V 3ph 50Hz
Total electrical load -per phase
Standard - as supplied 13.8
Maximum - selectable by installer 18
Weight 34.5
Model GR1500E 12/18kW
Low Speed
Maximum door width m 1.5
Maximum mounting height m 3
Maximum air volume m3/h 1730
Maximum velocity m/s 6.4
Motor power W 530
Noise level @ 3m free field dB(A) 52
Heating capacity - std/max1 kW 12/18
Electrical supply 415V 3ph 50Hz
Total electrical load -per phase
Standard - as supplied A 18.3
Maximum - selectable by installer A 26.6
Weight kg 52
Medium Speed
Maximum door width m 1.5
Maximum mounting height m 3
Maximum air volume m3/h 2268
Maximum velocity m/s 8.4
Motor power W 530
Noise level @ 3m free field dB(A) 55
Heating capacity - std/max1 kW 12/18
Electrical supply 415V 3ph 50Hz
Total electrical load -per phase
Standard - as supplied A 18.4
Maximum - selectable by installer A 26.8
Weight kg 52
High Speed
Maximum door width m 1.5
Maximum mounting height m 4
Maximum air volume m3/h 2700
Maximum velocity m/s 10
Motor power W 530
Noise level @ 3m free field dB(A) 59
Heating capacity - std/max1 kW 12/18
Electrical supply 415V 3ph 50Hz
Total electrical load -per phase
Standard - as supplied A 18.5
Maximum - selectable by installer A 27
Weight kg 52
Model GR2000E 18/24kW
Low Speed
Maximum door width m 2
Maximum mounting height m 3
Maximum air volume m3/h 2300
Maximum velocity m/s 6.4
Motor power W 730
Noise level @ 3m free field dB(A) 52
Motor power W 730
Noise level @ 3m free field dB(A) 52
Heating capacity - std/max1 kW 18/24
Electrical supply 415V 3ph 50Hz
Total electrical load -per phase
Standard - as supplied A 27.4
Maximum - selectable by installer A 35.7
Weight kg 64.5
Medium Speed
Maximum door width m 2
Maximum mounting height m 3
Maximum air volume m3/h 2880
Maximum velocity m/s 8
Motor power W 730
Noise level @ 3m free field dB(A) 55
Heating capacity - std/max1 18/24
Electrical supply 415V 3ph 50Hz
Total electrical load -per phase
Standard - as supplied 27.7
Maximum - selectable by installer 36
Weight 64.5
High Speed
Maximum door width m 2
Maximum mounting height m 4
Maximum air volume m3/h 3600
Maximum velocity m/s 10
Motor power W 730
Noise level @ 3m free field dB(A) 59
Heating capacity - std/max1 kW 18/24
Electrical supply 415V 3ph 50Hz
Total electrical load -per phase
Standard - as supplied A 27.8
Maximum - selectable by installer A 36.2
Weight kg 64.5